|
Courtesy:
http://www.p1m.com
Water Drying Tips Page 5
7.0) Water (drying):
(page 5 of 5)
7.32) HVAC Systems:
HVAC
systems have passageways that distribute clean air; be it fresh, makeup,
cooled or heated, to spaces that are generally occupied by persons, pets,
belongs, etc., while
bacteria,
mold (fungi) and contaminates foil the passageways intention.
The remediation of HVAC systems after a water loss should conform with
Sections 3.23.c,
3.23.d,
6.37,
6.37.a and
6.37.b, and the cleaning and remediation standards and guidelines
developed by the
National Air Duct Cleaning Association (NADCA).
7.33) Building Insulation: The remedial
actions best suited for insulation after a water loss would depend on the
insulations style, characteristics, if there is mold formation and the
severity of the damages caused by the water or moisture.
Mold (fungi) formation on
synthetic insulation is generally due to organic soiling as affixed to
the insulation during construction, such as wood dust.
When water or secondary damage has jeopardized the insulations R-value or
fire rating, it should be replaced.
Blanket and batt insulation constructed from fiberglass has an absorption
rate of 0.05% or less and could be dried when moderately affected by water
or moisture.
Additional remedial information on
building insulation can be found in
Section 6.21.n.
7.34) Drying Equipment: The loss type
(category/situation), surface types, and post-condition (what is wet? and
how wet is it?) would determine the type and quantity of equipment needed
to mitigate and neutralize a water loss site.
When determining the quantity of equipment needed, the number of rooms
affected, the cubic feet of affected rooms, temperature, humidity, rate of
wicking, and moisture content of building components and content items
should be used as a basis. When sizing dehumidification equipment, the
water site drying classifications in
Section 7.42 should be used as a starting point.
Equipment left on site in an operable state for a considerable amount of
time should be inspected at least once in a 24-hour period, and this should
include, but not be limited to; airmovers, dehumidifiers, generators, etc.,
and as conditions improve, pieces of equipment should be removed.
7.35) Pumps:
Pumps are used to move water from one area to another, and there are
several types of pumps available to achieve this goal:
- Low & high-pressure pumps
- Utility pumps
- Trash pumps
Utility pumps, a/k/a trench/ditch pumps are used to remove standing water at
several inches deep and some are submersible, while pressure and trash pumps
can remove water several feet deep.
Low & high pressure pumps can be self-priming, or need priming assistance.
Trash pumps are designed to move waters containing, mud, dirt, stones,
sticks, etc.
When pumping basements or lower levels after flooding, the ground pressure
outside the structure should be less than the pressure inside the structure
to prevent wall cracking or collapse of the structure.
Recommended pumping procedures for
basements is available at
MisterFixIt.com/Flood.htm.
Pumps are rated at
gallons per hour (GPH) and lift, and the
U.S. gallons into cubic feet table would be helpful when sizing pumps
and calculating time frames.
Each pump has its application, and pumps should only be
used for the applications they are
designed for.
7.36) Extraction Equipment: Extraction
machines would be portable or truck mount, and each has its benefits and
limits.
Truck mount units offer large volume extraction, but are limited on
multi-level properties, while portable units are emptied more often, yet are
versatile in multi-level properties.
Extraction equipment should be in excellent working order and spare parts,
such as jets, couplings, valves, etc. should be on hand.
7.37) Airmovers: There are several types of
airmovers designed specifically for structural drying:
- Turbofans
- Vortex Air Mover
- High Velocity Fans
- Low AMP Air Mover
Turbofans are designed at a low center of gravity to force air along floor
and wall surfaces, while axial fans are designed to force a large volume of
air across a large area.
Typically, one (1) airmover per 300 SF minimum when drying, or three
(3) airmovers per one (1) dehumidifier --- depending on the dehumidifiers
rate of evaporation. (ref.
7.38)
Professional brand airmovers have varying accessories available to aid with
the drying process:
- Turbovents
- Turboduct
- Mini-Turbovents
- Flexible Ducting
When performing water loss mitigation, residential box fans, circular
fans, etc. should not be used due to possible electrical shock or
electrocution.
7.38)
Dehumidifiers: Dehumidifiers
are available in
refrigerant or
desiccant, and the sizing of a refrigerant dehumidifier is based on
grains (gpp) of moisture it can draw from the air in a 24-hour period, and a
desiccant dehumidifier is sized by the CFM, as illustrated in
Table 7-G and
Table 7-I.
Refrigerant (coil) dehumidifiers condense moisture from the atmosphere onto
chilled coils, while desiccant dehumidifiers absorb the moisture from the
air.
Standard refrigerant dehumidifiers can operate at temperatures as low as 67º
F. Commercial dehumidifiers with hot gas bypass operate as low as 40º F.
Heat pump dehumidifiers operate down to 33º F. And desiccant dehumidifiers
operate down to 32º F or lower.
The sizing of dehumidifiers (refrigerant and desiccant) is listed within
Table 7-I, at the bottom of this page.
7.39) Chemical Dispensers: There are
several applicators available to dispense chemicals and cleaning agents:
- Ultra low volume (ULV) foggers
- Electric sprayers (airless)
- Hydo-Force injection sprayers
- Hand pump sprayers
- Trigger sprayers
Each dispenser is designed for a specific application such as; room volume,
surface area and within hidden cavities, and dispensers should only be used
for the applications they are designed for.
|
7.40) Injection Drying:
Injection drying equipment as manufactured by
Injectidry Systems and
Dri-Eaz Products are pressure drying equipment that offer both positive
and negative pressure.
Injection drying
equipment when used in the right application and set up properly will reduce
the size of access hole penetrations in walls, cabinetry, and flooring
materials as well as reduce drying time and prevent secondary damages.
7.41)
Meters and Instruments:
Contractors will use several types of meters
and instruments during mitigation:
- HydoSensor moisture probe
- Thermo-Hygrometer
- Moisture meter (penetrating and non-penetrating)
- Psychrometric calculator
- Dehumidifier calculator
- Thermal Imaging
The hydrosensor, penetrating meter and non-penetrating meter operate as
continuity meters and provides reading when a DC volt circuit is completed.
Thermal imaging camera uses infrared technology, providing a heat
differential.
7.42)
Loss Site (Drying)
Classification: During the evaluation of a water loss site,
technicians should determine the drying classification as set forth by the
IICRC. The classifying of a water loss site by its evaporation rate, as
affected by the permeance of the structures building components and content
items, should provide technicians a starting point on dehumidification
needed.
Table 7-A provides a brief listing of building material permeance.
The four
IICRC water damage classifications are as follows:
Class 1: Slow Evaporation Rate:
Water losses that affect only part of a room or area, or losses with lower
permeance/porosity materials (e.g., plywood, particle board, structural
wood,
VCT, concrete). Little or no wet carpet or cushion is present. Minimum
moisture is absorbed by materials, releasing moisture slowly.
Class 2: Fast Evaporation Rate: Water losses that affect an entire
room or carpet and cushion. Water has
wicked up walls 12" - 24”. There is moisture remaining in structural
materials (e.g., plywood, particleboard, structural wood, concrete).
Class 3: Fastest Evaporation Rate:
Water may have come from overhead.
Ceilings, walls, insulation, carpet, cushion and sub-floor in the entire
area are
saturated.
Class 4: Specialty Drying Situations: These consist of wet materials
with very low permeance/porosity (hardwood,
plaster, brick, concrete, stone, crawlspace). Typically, there are deep
pockets of saturation, which requires very low specific humidity.
Technicians should evaluate the water loss site to determine their
psychrometrics, materials permeance, etc., and base their dehumidification
on the cubic foot of air within the affected areas based on the following
steps:
Step 1: Calculate the affected areas into cubic feet.
Step 2: Determine water loss Class (#1, #2, #3, or #4).
Step 3: Calculate total number of pints dehumidification equipment
will remove based on
Association of Home Appliance Manufacturers (AHAM) test conditions at
80° F / 60% Rh.
Step 4: Based on AHAM performance per 24 hours, the total
dehumidification needed should be calculated by dividing the factor into the
total cubic feet of the area being dried as shown in
Table 7-I.
The Classifying of water damages as explained in this section should only be
a starting point based on the loss site evaluation and conditions.
Adjustments should be made as determined by daily drying records and loss
site conditions as they change.
7.43) Heat (convection) Drying Systems:
As described in
Section 7.11.a, temperature could be considered the balance point of a
drying system, since moisture, water and the materials that make up the
built environment all react to heat.
When using heat to mitigate (dry) a structure, the interior atmospheric
temperature should be maintained between 95° F to 105°
F. While interior atmospheric temperatures maintained at
105° F
to 110°
F, when properly set-up and monitored should reduce drying
time. (ref. Section
7.43.c)
Convection (heat) drying systems can reduce structural drying time by
10% to 30% at minimum, depending on what is wet?, the materials saturation
and the experience the drying technician has with the drying system, as well
as with the built environment that is being dried.
For a heat drying system to be efficient and prevent secondary damages,
air movement and
air exchanges should be part of the heat systems
equation:
Forced
Convection = Heat + Air Movement + Air Exchanges
The heat drying process should
operate as a convection system, where the moisture is transported to the
exterior of a structure through air changes.
When drying with
heat, 3 to 4 air exchanges per hour is recommended. Moreover, uniform heat
throughout a wet structure is recommended during the drying process, and
supplemental low grain dehumidifiers should be used to gain uniformity, when
required.
7.43.a)
Net-Positive Pressure:
Since moist air will travel to dry air, when it can. Heat drying systems
should maintain a net-positive pressure during the drying process when the
specific humidity produced by the drying system is lower than the relative
humidity at the exterior of a structure, which would produce excess
infiltration if the drying system is not properly balanced. (ref.
7.15.a)
7.43.b)
Heat Precautions:
Temperatures in excess of 95° F, when used to dry a structure, would require
a pre-evaluation of the property being heated to determine what may or may
not be affected by heat.
Items such as
painting, pictures, books, candles, musical instruments, antiques, etc.
should be classified at low heat sensitive and should be protected or
removed during the heat drying process.
When ducting
heat, flexible ducting should be insulated to prevent damage to grass,
shrubbery, window sashes, doorways, etc.
Fire suppression systems (i.e., fire sprinkler, halon, fire alarms &
smoke detectors, etc.) could require protective means or be disarmed before
the heat drying process begins.
Before a fire
suppression system is altered, protected or disarmed, the local fire
authority, manufacturer of the fire suppression system and all
occupants of the building should be notified.
When using heat
drying systems, the manufacturers use practices, safety precautions, and
heat sensitive materials listing should be followed.
Heat drying
system manufacturers and technicians are encouraged to develop a universal
materials heat sensitivity chart for the mitigation, remediation and
restoration industries.
7.43.c)
Drying System Manufacturers:
The following firms offer heat drying systems:
-
Aquadry Systems, LLC
-
TES Drying System
-
ThermaPureHeat
-
Water Out
7.43.d) Other Heat Applications: Due to
the
characteristics of heat --- heat systems can also be used as:
- Supplemental system to kill mold spores, in lieu of disinfectants(1)
(2)
- Pasteurization for treating bacteria, in lieu of disinfectants (2)
- Document drying system, when documentation is wet/flooded due
to sewage back-flow (2)
- Extermination, in lieu of pesticides (2)
- Odor removal (3)
(1) Does not supplement the physical removal of mold spores.
(2) An industrial hygienist should always be consulted when using heat for
mold, bacteria, sewage or extermination.
(3) Does not supplement the physical removal of the odor source.
When using heat for disinfecting, the contaminate being treated would
determine the heat reaction time required.
For additional information on using heat for other
processes, see Section 8.0. (coming soon) |